12.0 CLASS 3200 PROTOCOL DEFINITIONS

ModBus Customer Point Map: CL3200

Address Registers Format

Description

Units

CL

3200

40001

1

2

Integer Energy delivered

Wh Pulse

R/W

40001

1

2

Integer Energy received

Wh Pulse

R/W

40005

1

2

Integer Reactive energy delivered

VARh Pulse R/W

40007

1

2

Integer Reactive energy received

VARh Pulse R/W

41001

1

2

Float

Energy delivered

kWh

R/W

41003

1

2

Float

Energy received

kWh

R/W

41005

1

2

Float

Reactive energy delivered

kVARh

R/W

41007

1

2

Float

Reactive energy received

kVARh

R/W

41009

2

Float

Real power

kW

R

41011

2

Float

Reactive power

kVAR

R

41013

2

Float

Apparent power

kVA

R

41015

2

Float

Power factor

% PF

R

41017

2

Float

Peak demand

kW

R

41019

2

Float

Current average

Amps

R

41021

2

Float

Voltage line-neutral

Volts-N

R

41023

2

Float

Voltage line-line

Volts-L

R

41025

2

Float

Frequency

Hz

R

41027

2

Float

Phase angle

Degree

R

41029

2

Float

Real power, phase A

kW

R

41031

2

Float

Real power, phase B

kW

R

Advertising