Wiring

3.1

Notes on Wiring

[1] Provide noise elimination measures for the electrical devices located along the same power-supply

path or in the same system according to the operation manuals for the X-SEL controller, RC controller

and ROBONET.

[2] If multiple power-supply units are used to supply 24V DC power to RC controllers, connect the 0V

lines of the power supplies for respective controllers.

[3] Be sure to shield the communication cable. Connect the cable’s shield to a single point ground.

[4] Make sure emergency stop signals are input simultaneously to the X-SEL and each RC controller

/ROBONET. If the emergency stop timing of the X-SEL varies from that of the RC controller/ROBONET

by a specified time (approx. 5 seconds) or longer, the X-SEL will generate an error “6B4: RC gateway

emergency stop inconsistency error”

(Note 1)

and enter the emergency stop mode (cold-start level).

Note1 Ɣ Connecting some ERC2 controllers or avoiding this error detection on other controllers, set

bits 0 to 3 of the X-SEL controller’s I/O parameter No. 507 to “1.”

(The setting of I/O Parameter No. 507 is available in V0.90 or later for X-SEL P/Q and

V0.42 or later for X-SEL PX/QX. Refer to 6.1 for details.)

Ɣ If the RC controller is connected via the X-SEL, this error will not occur.

Emergency stop ON!

0V common)

+

Power

supply 1

Power

supply 2

+

(