2 example for parameter settings – IAI America XSEL-S User Manual

Page 25

Advertising
background image

3. XSEL-R/S/RX/SX/RXD/SXD

19

3.5.2 Example for Parameter Settings

(1) Example for when using only EtherCAT®

It is how to establish the setting when using EtherCAT® to 16 ports of each input and output

from the top of the standard I/O ports, and no other I/O port (for I/O board, etc.) is to be used.















� I/O Parameter

No.

Parameter name

Default

(reference) Input Range Unit

Remarks

1 I/O Port Allocation Type

0

0 to 1

0

0: Fixed Allocation

1: Automatic Allocation

• Reference 1

Priority of I/O Port

Assignment when

automatically assigned

Port No.

(No.0 to 299/No.300 to 599)

1)

Network I/F Module 1

2)

I/O slot 1 (I/O1) Mounting board

3)

I/O slot 2 (I/O2) Mounting board

*

Assigned for the range of continuous

mounting from I/O slot 1 (I/O1)

Mounting board

• Reference 2

Priority of extension I/O ports

at automatic assignment

Port No.

(No.1000 to 3999/

No.4000 to 6999)

1)

Network I/F Module 2

2)

Extension I/O Unit

3)

Communication between IA Net

Controllers

2 Standard I/O Fix-Allocated Input

Port Start No.

0

-1 to 599

-1

0+(Multiples of 8)

[Ineffective when -1 is selected]

3 Standard I/O Fix-Allocated Output

Port Start No.

300

-1 to 599

-1

300+(Multiples of 8)

[Ineffective when -1 is selected]

10 Standard I/O Error Monitoring

(I/O1)

1

0 to 5

0

0:

No Monitoring (Not to use I/O board)

1:

Monitoring

2:

Monitoring (Not to monitor 24V I/O power

related error)

3:

Monitoring (To monitor only 24V I/O

power related error)

14 Network I/F Module 1

Remote Input Ports

256

0 to 256

16 8 port unit

15 Network I/F Module 1

Remote Output Ports

256

0 to 256

16 8 port unit

Not to be used

(I/O Board)

Standard Input Port No.0 to 15

Standard Output Port No.300 to 315

(EtherCAT® Board)