I/o parameters, Appendix – IAI America TT-C3 User Manual

Page 292

Advertising
background image

282

INTELLIGENT ACTUATOR

Appendix

Appendix

1. I/O

Parameters

No. Parameter

name

Default value

(Reference)

Input range

Unit

Remarks

1 I/O

port

assignment

type

0

Reference only

0: Fixed assignment

2

Input port start number
with fixed standard I/O1
assignments

000

-1 to 599

0 + (Multiple of 8) (Invalid if a negative value is set)
* Keep the default value if the main application version is

0.18 or earlier.

(Change prohibited)

3 Output

port

start

number with fixed
standard I/O1
assignments

300

-1 to 599

300 + (Multiple of 8) (Invalid if a negative value is set)
* Keep the default value if the main application version is

0.18 or earlier.

(Change prohibited)

4

Input port start number
with fixed expanded
I/O2 assignments

32

-1 to 599

0 + (Multiple of 8) (Invalid if a negative value is set)
* Keep the default value if the main application version is

0.18 or earlier.

(Change prohibited)

5 Output

port

start

number with fixed
expanded I/O2
assignments

316

-1 to 599

300 + (Multiple of 8) (Invalid if a negative value is set)
* Keep the default value if the main application version is

0.18 or earlier.

(Change prohibited)

6

Input port start number
with fixed expanded
I/O1 assignments
(Network I/F module)

-1

-1 to 599

0 + (Multiple of 8) (Invalid if a negative value is set)

7 Output

port

start

number with fixed
expanded I/O1
assignments (Network
I/F module)

-1

-1 to 599

300 + (Multiple of 8) (Invalid if a negative value is set)

8

For future expansion

-1

-1 to 599

9

For future expansion

-1

-1 to 599

10 Standard

I/O1

error

monitor

1

0 to 5

0: Do not monitor
1: Monitor
2: Monitor (Do not monitor errors relating to 24-V I/O power

source)

3: Monitor (Monitor only errors relating to 24-V I/O power

source)

* Some exceptions apply.

11

Expanded I/O2 error
monitor

1

0 to 5

0: Do not monitor
1: Monitor
2: Monitor (Do not monitor errors relating to 24-V I/O power

source)

3: Monitor (Monitor only errors relating to 24-V I/O power

source)
* Some exceptions apply.

12

Expanded I/O1 error
monitor (Network I/F
module)

1

0 to 5

0: Do not monitor
1: Monitor

* Some exceptions apply.

13

For future expansion

1

0 to 5

14

Number of ports using
network-I/F-module
remote input

0

0 to 240

Refer to the operation manual for each network I/F card
(CC-Link, DeviceNet, etc.).

15

Number of ports using
network-I/F-module
remote input

0

0 to 240

Refer to the operation manual for each network I/F card
(CC-Link, DeviceNet, etc.).

16

(For future expansion =
Change prohibited)

0

0 to 256

Multiple of 8

17

(For future expansion =
Change prohibited)

0

0 to 256

Multiple of 8

18 to

19

(For expansion)

0

20

Input filtering periods

2

1 to 9

msec

Input signal is recognized when the status is held for twice
the period set by this parameter.

21

Register input filtering
periods

2

1 to 9

msec

Input signal is recognized when the status is held for twice
the period set by this parameter.

22

For future expansion

2000

Reference only

msec