Zone output

A signal can be output when the actuator has entered a desired zone specified by the user.
Three parameters must be set to specify a zone.
A zone is set for each axis.

No.

Parameter name

Default value

Input range

Unit

86 Zone 1 MAX

0

-99999999 ~ 99999999

0.001 mm

87 Zone 1 MIN

0

-99999999 ~ 99999999

0.001 mm

88 Zone 1 output number

0

0 ~ 899

None

Axis-specific parameter No. 86, “Zone 1 MAX”
Set the maximum limit of the zone, in units of 0.001 mm.

Example: To set 50 mm, set the value “50000.”

Axis-specific parameter No. 87, “Zone 1 MIN”
Set the minimum limit of the zone, in units of 0.001 mm.

Example: To set 10 mm, set the value “10000.

Axis-specific parameter No. 88, “Zone 1 output number”
Set an output port or flag number for the zone.
The output number set in this parameter cannot be used in programs.

z Note

Set the zone so that the passing time through the zone will become at least 3 msec.

(Axis-specific
parameter No. 86)

MAX side

Set an output range.
(A signal is output while the actuator is
passing through this range.)

Passing status ON

(Axis-specific parameter No. 88)

MIN side

(Axis-specific
parameter No. 87)

Actuator