Part 1 Installation

B. Motor power

100 VAC or
200 VAC

Circuit

breaker

Clamp filters

Surge protector

Earth

leakage

breaker

Noise

filter

Class D grounding

(former Class 3

grounding)

24-VDC

power

supply

Brake

release box

PIO connector

Brake power input connector

Controller

AC power input
connector

A. Control power

6. Power

Auxiliary

Select and install appropriate power auxiliaries according to the illustration and explanations provided below.
If your product requires CE Marking certification, take proper actions by referring to “CE Marking.”

6.1 Example of Configuration of Power Auxiliaries

[1] Circuit

breaker

Install a circuit breaker or earth leakage breaker in the AC power-supply line (primary side) of the controller in
order to prevent damage due to power switching and short current. One circuit breaker or earth leakage breaker
can be used to protect both the motor power supply and control power supply.

x While the actuator is accelerating or decelerating, the controller current increases to three times the

rated current. Select an appropriate circuit breaker that will not trip when this higher current flows. If the
circuit breaker you have selected trips, change it to one with the next higher level of rated current.

x Select a circuit breaker that will not trip due to rush current. [Refer to the graph of operating

characteristics in the manufacturer’s catalog.]

x The rated cutoff current of the selected circuit breaker must be enough to cut off any short-circuit current,

should it flow, without fail.
Rated cutoff current > Short-circuit current = Power-supply capacity on primary side / Power-supply
voltage

x The rated current of the selected circuit breaker should have an ample allowance.

Rated current of circuit breaker > (Rated motor power-supply capacity [VA] + Control power-supply
capacity [VA]) / AC input voltage x Safety factor (rough guide: 1.2 to 1.4)

Rated current of circuit breaker > (Rated motor power-supply capacity [VA] + Control power-supply
capacity [VA]) / AC input voltage x Safety factor (rough guide: 1.2 to 1.4)

[2] Earth leakage breaker
Install an earth leakage breaker on the AC power-supply line side (primary side) of the controller to cut off earth
leakage current. One earth leakage breaker may be used to serve both the motor power and plant power.

x You must select an appropriate earth leakage breaker that can meet your specific purpose, be it fire

protection, protection of human life, or the like. Also measure the earth leakage current at the location
where the earth leakage breaker is to be installed.

x The earth leakage current changes according to the capacity of the motor to be connected, lengths of

cables, and surrounding environment. So that proper earth leakage protection can be provided, measure
the earth leakage current at the location where the earth leakage breaker is to be installed.

x Use an earth leakage breaker of harmonic type.