Digital output modules sx5l-sbt16k1 / sx5l-sbt16s1 – IDEC SX5L Series User Manual

Page 17

Advertising
background image

2: H

ARDWARE

S

PECIFICATIONS

2-6

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

Digital Output Modules SX5L-SBT16K1 / SX5L-SBT16S1

General Specifications

Transistor Output Specifications

Rated Power Voltage

24V DC

Power Voltage Range

21.6 to 26.4V DC (including 5% ripple)

Power Consumption

1.2W (24V DC)

Power Inrush Current

3A maximum (24V DC)

Allowable Momentary Power Interruption

10 ms minimum (at the rated power voltage)

Dielectric Strength

1,000V AC, 1 minute between power and FG terminals

Insulation Resistance

100 M

Ω minimum between power and FG terminals (500V DC megger)

Operating Temperature

0 to 55°C (no freezing)

Operating Humidity

30 to 90% RH (non-condensing)

Storage Temperature

–20 to +75°C (no freezing)

Storage Humidity

30 to 90% RH (non-condensing)

Pollution Degree

2 (IEC 60664)

Corrosion Immunity

Atmosphere free from corrosive gases

Altitude

Operation: 0 to 2,000m
Transpor t: 0 to 3,000m

Vibration Resistance

10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 m/s

2

2 hours per axis on each of three mutually perpendicular axes

Shock Resistance

294 m/s

2

, 11-ms sinusoidal half-wave pulse

Mounting

35-mm-wide DIN rail, direct panel mounting (M4 mounting screws)

Weight (approx.)

240g

Type No.

SX5L-SBT16K1

SX5L-SBT16S1

Output Points

16 points

Output Type

N-MOS open drain (NPN transistor output)

P-MOS open drain (PNP transistor output)

Rated Load Voltage

24V DC

Load Voltage Range

21.6 to 26.4V DC

Maximum Load Current

500 mA per point
6A per common line

Output Common Polarity

Plus common

Minus common

Voltage Drop (ON Voltage)

0.8V maximum
(voltage between the power – terminal and
output terminals when output is on)

0.8V maximum
(voltage between the power + terminal and
output terminals when output is on)

Leakage Current

1 mA maximum

Isolation from Power Line

Photocoupler isolation

Dielectric Strength

500V AC, 1 minute between output and FG terminals
500V AC, 1 minute between output and power terminals

Insulation Resistance

100 M

Ω minimum between output and FG terminals (500V DC megger)

100 M

Ω minimum between output and power terminals (500V DC megger)

Advertising