Troubleshooting diagram 8 – IDEC SX5L Series User Manual

Page 61

Advertising
background image

5: T

ROUBLESHOOTING

5-8

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

Troubleshooting Diagram 8

Communication seems incomplete.

NO

YES

YES

NO

Is the hear tbeat

transmission inter val

shor t?

NO

YES

Expand the hear tbeat transmission inter val des-
ignated in the output network variable configura-
tion proper ty to reduce the traffic.

NO

YES

Replace the SX5L or call IDEC for assistance.

Adjust the output network configuration proper-
ties, such as the minimum transmission inter val
and minimum change to send output variables.

Is the FG terminal

connected to the ground

correctly?

YES

NO

Connect the FG terminal to a proper ground
correctly. See page 3-2.

Are analog value data

sent frequently?

Are pulse

count current value data

sent frequently?

Adjust the output network configuration proper-
ties, such as the hear tbeat transmission inter-
val, minimum transmission inter val, and enable
event-driven transmission.

Is a loop made

by vir tual I/O functional

blocks?

Bind functional blocks without making a loop.

Is there influence

of external noise?

YES

Keep away from external noise and confirm
operation again.

NO

Note: To confirm data transmission, use a protocol analyzer.