Analog Input Functional Block

Analog input channels 0 through 3 correspond to nvoAI0 through nvoAI3, respectively. At the factory settings, analog
input signals of 1 to 5V or 4 to 20 mA are converted to 1 through 100%, and the result is sent to the network.

The output network variable type of the Analog Input functional block can be changed to various SNVTs as shown on
page 4-11.

I/O

Name

Type

Description

Output Network Variable

nvoAI0

SNVT_lev_percent

Corresponds to channel 0

nvoAI1

SNVT_lev_percent

Corresponds to channel 1

nvoAI2

SNVT_lev_percent

Corresponds to channel 2

nvoAI3

SNVT_lev_percent

Corresponds to channel 3

Configuration Property

nciMaxStsSendT1

SCPTmaxSndT

nvoAI0 to nvoAI3 hear tbeat transmission inter val
(factor y setting: 3 minutes)

nciMinSendT1

SCPTminSndT

nvoAI0 to nvoAI3 minimum transmission inter val
(factor y setting: 1 second)

nciMaxRng[0]

SCPTmaxRnge

Designates nvoAI0 maximum value
(factor y setting: 100%)

nciMaxRng[1]

SCPTmaxRnge

Designates nvoAI1 maximum value
(factor y setting: 100%)

nciMaxRng[2]

SCPTmaxRnge

Designates nvoAI2 maximum value
(factor y setting: 100%)

nciMaxRng[3]

SCPTmaxRnge

Designates nvoAI3 maximum value
(factor y setting: 100%)

nciMinRng[0]

SCPTminRnge

Designates nvoAI0 minimum value
(factor y setting: 0%)

nciMinRng[1]

SCPTminRnge

Designates nvoAI1 minimum value
(factor y setting: 0%)

nciMinRng[2]

SCPTminRnge

Designates nvoAI2 minimum value
(factor y setting: 0%)

nciMinRng[3]

SCPTminRnge

Designates nvoAI3 minimum value
(factor y setting: 0%)

nciMinDelta[0]

SCPTsndDelta

Minimum change to send nvoAI0
(factor y setting: 0%)
valid for ever y input level

nciMinDelta[1]

SCPTsndDelta

Minimum change to send nvoAI1
(factor y setting: 0%)
valid for ever y input level

nciMinDelta[2]

SCPTsndDelta

Minimum change to send nvoAI2
(factor y setting: 0%)
valid for ever y input level

nciMinDelta[3]

SCPTsndDelta

Minimum change to send nvoAI3
(factor y setting: 0%)
valid for ever y input level

AI

nvoAI0

nvoAI1

nvoAI2

nvoAI3