Troubleshooting Diagram 4

Commissioning is impossible.

YES

NO

Is the PWR LED on?

NO

Is the network

inter face connector inser ted

completely?

YES

Is the network cable

connected correctly?

YES

YES

NO

Is the

transmission distance within

the limit?

YES

Does the XIF match

the XIF No. indicated on the

SX5L front?

YES

NO

NO

NO

Inser t the network inter face connector to the
bottom.

Without a terminator, stable communication may
not be ensured. Install one or two terminators
correctly. See pages 1-6 and 3-3.

Attach ferrules to the L

ON

W

ORKS

cable ends, and

connect the cable to the connector correctly.

See Troubleshooting Diagram 1,
“The PWR LED does not go on.”

Is a terminator

installed correctly?

Keep the transmission distance within the limit.
See page 2-3.

Download the XIF file for your SX5L from the
IDEC web site or call IDEC for assistance.

Is data

transmitted from the

management tool?

NO

YES

Is the network traf fic high?

YES

NO

Is there influence

of external noise?

YES

Send data from the management tool.

Note: To confirm data transmission, use a protocol analyzer.

Reduce the network traf fic and retr y commi-
sioning.

Keep away from external noise and confirm
operation again.

NO

Replace the SX5L or call IDEC for assistance.

Note: To confirm data transmission, use a protocol analyzer.