Network Cable Wiring

Applicable Cables

Use twisted pair cable with core wires of AWG24 to AWG14 (0.2 to 2.5 mm

2

) applicable to the L

ON

W

ORKS

network. One

or two wires can be connected to one network interface connector. When connecting two wires together, use wires of the
same size, AWG24 to AWG16 (0.2 to 1.5 mm

2

). Whether connecting one or two wires, always use ferrules to terminate the

wires for connection to the network interface connector.

Network Interface Connector

The network interface connector features spring-clamp terminals. Push in the
orange pin to open the cable hole using a flat screwdriver, and insert a ferrule
into the cable hole. The L

ON

W

ORKS

network cable can be connected to the

two terminals in either polarity.

For tightening the mounting screws of the network interface connector, use a
flat screwdriver with a straight shank at the tip.

Recommended Screwdriver: Phoenix Type No. SZS 0,6 x 3,5

(Order No.: 12 05 05 3)

Tightening Torque

Tighten the network interface connector mounting screws to a torque of 0.3 to 0.5 N·m.

Applicable Ferrules

Terminators

L

ON

W

ORKS

networks require terminators. Connect terminators consisting of one resistor and two

capacitors shown at right (note the polarity of capacitors).

The bus topology requires two terminators at both ends of the network, and the free topology can
connect a terminator at any position in the network.

Wire Thickness

Phoenix Type (Order No.)

AWG

Cross Section (mm

2

)

For 1-cable connection

For 2-cable connection

24

0.25

AI 0,25-8 YE (32 00 85 2)

20

0.5

AI 0,5-8 WH (32 00 01 4)

AI-TWIN 2 x 0,5-8 WH (32 00 93 3)

18

0.75

AI 0,75-8 GY (32 00 51 9)

AI-TWIN 2 x 0,75-8 GY (32 00 80 7)

18

1.0

AI 1-8 RD (32 00 03 0)

AI-TWIN 2 x 1-8 RD (32 00 81 0)

16

1.5

AI 1,5-8 BK (32 00 04 3)

AI-TWIN 2 x 1,5-8 BK (32 00 82 3)

14

2.5

AI 2,5-8 BU (32 00 52 2)

Topology

Bus Topology

Free Topology

R

105

Ω±1%, 1/8W

52.3

Ω±1%, 1/8W

C1 and C2

100 µF,

≥50V

100 µF,

≥50V

Connect Position

Terminators at both ends of the network

One terminator at any position in the network

Applicable Terminator

Echelon 44101

Echelon 44100

Caution

• Do not run the network cable in parallel with or in the vicinity of power, output, or motor lines.

Keep the network cable away from noise sources. Check for loose connection periodically. Loose
connection may cause overheat, resulting in possible fire hazard.

Orange Pin

6.0

8.0

For 1-cable connection

For 2-cable connection

7.0

8.0

AI 1-8 RD

AI-TWIN 2 x 1-8 RD

To crimp the ferrules, use a special crimping tool.

Crimping Tool: Phoenix Type No. CRIMPFOX ZA 3

(Order No.: 12 01 88 2)

+

R