Pulse input module sx5l-sbcn081 – IDEC SX5L Series User Manual

Page 27

Advertising
background image

2: H

ARDWARE

S

PECIFICATIONS

2-16

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

Pulse Input Module SX5L-SBCN081

General Specifications

Pulse Input Specifications

Rated Power Voltage

24V AC (50/60Hz) / 24V DC compatible

Power Voltage Range

21.6 to 26.4V AC/DC (including 5% ripple)

Power Consumption

2.0 VA (24V AC), 1.0W (24V DC)

Power Inrush Current

15A maximum (24V AC/DC)

Allowable Momentary Power Interruption

10 ms minimum (at the rated power voltage)

Dielectric Strength

1,000V AC, 1 minute between power and FG terminals

Insulation Resistance

100 M

Ω minimum between power and FG terminals (500V DC megger)

Operating Temperature

0 to 55°C (no freezing)

Operating Humidity

30 to 90% RH (non-condensing)

Storage Temperature

–20 to +75°C (no freezing)

Storage Humidity

30 to 90% RH (non-condensing)

Pollution Degree

2 (IEC 60664)

Corrosion Immunity

Atmosphere free from corrosive gases

Altitude

Operation: 0 to 2,000m
Transpor t: 0 to 3,000m

Vibration Resistance

10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 m/s

2

2 hours per axis on each of three mutually perpendicular axes

Shock Resistance

294 m/s

2

, 11-ms sinusoidal half-wave pulse

Mounting

35-mm-wide DIN rail, direct panel mounting (M4 mounting screws)

Weight (approx.)

250g

Input Points

8 points

Rated Input Voltage

24V DC

Input Voltage Range

0 to 26.4V DC

Minimum Pulse Width

ON duration:

50 ms

OFF duration: 50 ms

Maximum Frequency Response

8 Hz

Input Impedance

Approx. 3.4 k

Input Current

7 mA/point (24V DC)

No. of Common Circuits

1 common circuit/point

Input Common Polarity

Plus and minus common compatible

Input Turn ON Voltage

15V minimum (between input and COM terminals)

Input Turn OFF Voltage

5V maximum (between input and COM terminals)

Isolation from Power Line

Photocoupler isolation

Dielectric Strength

500V AC, 1 minute between input and FG terminals
500V AC, 1 minute between input and power terminals
500V AC, 1 minute between input terminals

Insulation Resistance

100 M

Ω minimum between input and FG terminals (500V DC megger)

100 M

Ω minimum between input and power terminals (500V DC megger)

100 M

Ω minimum between input terminals (500V DC megger)

Current Value Backup Times

10,000 times of current value storage into the built-in EEPROM during
power interruption

Advertising