Troubleshooting diagram 7 – IDEC SX5L Series User Manual

Page 60

Advertising
background image

5: T

ROUBLESHOOTING

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

5-7

Troubleshooting Diagram 7

Analog data accuracy is not satisfactory.

YES

NO

NO

Is the input device

connected correctly?

YES

Are unused

channel terminals connected

together?

YES

YES

NO

Is the network variable

type changed?

NO

NO

YES

Data may not be transmitted. Set correct values
to the hear tbeat inter vals, minimum transmis-
sion inter vals, and minimum change to send out-
put variables.

Connect together the terminals of an unused
channel using an optional jumper or wire.
See pages 2-13 and 2-15.

Connect an output device to meet the input
specifications of the SX5L.

Is configuration

proper ty designated

correctly?

Set the type change and configuration
proper ty of the network variable cor-
rectly.

Does the connected

device output correct

values?

NO

YES

Is there influence

of external noise?

YES

Keep away from external noise and confirm
operation again.

NO

Replace the SX5L or call IDEC for assistance.

Analog Input Module and Pt100

Ω Input Module

Does the

connected device output meet

the SX5L input?

Connect the input device to the SX5L correctly.

Is the network

variable type changed

correctly?

NO

Check that the connected device generates output values correctly.
Use the measuring instrument correctly.

Make sure that the analog output device gener-
ates correct output values.

YES

Advertising