Troubleshooting, Roubleshooting, Introduction – IDEC SX5L Series User Manual

Page 54

Advertising
background image

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

5-1

5: T

ROUBLESHOOTING

Introduction

This chapter describes the procedure to determine the cause of trouble and actions to be taken when any trouble occurs
while operating the SX5L communication terminals.

Troubleshooting Diagram 1

The PWR LED does not go on.

YES

NO

Is AC or DC power

supplied correctly?

NO

Is the terminal block

inser ted completely?

YES

Is the power voltage

21.6 to 26.4V?

YES

Is DC power used?

YES

NO

Are the

module power and I/O power

shor ted?

Is the DC power

polarity correct?

YES

Do the module

power and I/O power use the

same source?

NO

YES

Wire the power correctly.

Inser t the terminal block to the
bottom.

NO

Supply power voltage of 21.6 to
26.4V AC or DC, accordingly.

NO

Connect the DC power correctly.

NO

YES

Replace the SX5L or call IDEC for
assistance.

Make sure of correct power termi-
nals for the SX5L internal circuit and
I/O circuits.

Replace the SX5L or call IDEC for
assistance.

Supply AC or DC power correctly.

Advertising