2-8

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

Digital I/O Modules SX5L-SBM16K1, -SBM16K2, -SBM16S1, -SBM16S2

General Specifications

Digital Input Specifications

Rated Power Voltage

24V DC

Power Voltage Range

21.6 to 26.4V DC (including 5% ripple)

Power Consumption

1.2W (24V DC)

Power Inrush Current

3A maximum (24V DC)

Allowable Momentary Power Interruption

10 ms minimum (at the rated power voltage)

Dielectric Strength

1,000V AC, 1 minute between power and FG terminals

Insulation Resistance

100 M

Ω minimum between power and FG terminals (500V DC megger)

Operating Temperature

0 to 55°C (no freezing)

Operating Humidity

30 to 90% RH (non-condensing)

Storage Temperature

–20 to +75°C (no freezing)

Storage Humidity

30 to 90% RH (non-condensing)

Pollution Degree

2 (IEC 60664)

Corrosion Immunity

Atmosphere free from corrosive gases

Altitude

Operation: 0 to 2,000m
Transpor t: 0 to 3,000m

Vibration Resistance

10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 m/s

2

2 hours per axis on each of three mutually perpendicular axes

Shock Resistance

294 m/s

2

, 11-ms sinusoidal half-wave pulse

Mounting

35-mm-wide DIN rail, direct panel mounting (M4 mounting screws)

Weight (approx.)

240g

Type No.

SX5L-SBM16K1 / SX5L-SBM16K2

SX5L-SBM16S1 / SX5L-SBM16S2

Input Points

8 points

Input Type

NPN input type
No-voltage input (DC 2-wire sensor, NPN
3-wire sensor, no-voltage contact)

PNP input type
No-voltage input (DC 2-wire sensor, PNP
3-wire sensor, no-voltage contact)

Rated Input Voltage

24V DC

Input Voltage Range

0 to 26.4V DC

Input Impedance

Approx. 4.0 k

Input Current

6 mA/point (24V DC)

No. of Common Circuits

1

Input Common Polarity

Minus common

Plus common

Input Delay Time

250 ms

Input Turn ON Voltage

15V minimum (between input and COM terminals)

Input Turn OFF Voltage

5V maximum (between input and COM terminals)

Input OFF Current

1 mA maximum

Isolation from Power Line

Photocoupler isolation

Dielectric Strength

500V AC, 1 minute between input and FG terminals
500V AC, 1 minute between input and power terminals

Insulation Resistance

100 M

Ω minimum between input and FG terminals (500V DC megger)

100 M

Ω minimum between input and power terminals (500V DC megger)

Advertising