IDEC SX5L Series User Manual

Page 64

Advertising
background image

A

PPENDIX

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

A-3

Network management tool

A tool used to perform network management.

Network variable

A data item that a particular device application program expects to get from other device on a network (an input network
variable) or expects to make available to other devices on a network (an output network variable). Examples are a temper-
ature, switch value, and actuator position setting.

Neuron Chip

A microprocessor that supports LonTalk protocol. The SX5L uses Toshiba TMPN3120FE5M with a 10-MHz clock quartz
oscillator.

Neuron ID

Every L

ON

W

ORKS

device has a unique 48-bit identifier called the Neuron ID. The Neuron ID is typically assigned when a

device is manufactured and used for network management.

Node ID

The third layer of the device address. Node ID identifies an individual device within a subnet. Up to 127 devices can be
defined within a single subnet.

Protocol analyzer

Software or hardware that enables to monitor the data transmitted through the network.

SCPT

An acronym for Standard Configuration Property Type. SNVTs are standardized definitions of the units, scaling, encoding,
and meaning of the contents of configuration properties.

SNVT

An acronym for Standard Network Variable Type. SNVTs are standardized definitions of the units, scaling, and encoding
of the contents of network variables.

SNVT_elapsed_tm

SNVT index 87, used to measure elapsed time. The SX5L uses SNVT_elepsed_tm for configuration property nciMaxSts-
SendT to determine the heartbeat transmission intervals.

SNVT_lev_percent

SNVT index 81, used to represent data in percent. The SX5L uses SNVT_lev_percent for output network variables
nvoAI0 through nvoAI3 of the Analog Input functional block. When the measured value exceeds the limit, 0x7FFF is sent.

Measurement

Type Size and Structure

Size

Valid Type Range

Note

Elapsed Time

7 bytes

typedef struct {

unsigned long

day;

unsigned short

hour;

unsigned short

minute;

unsigned short

second;

unsigned long

millisecond;

} SNVT_elapsed_tm;

day

0 .. 65,534

65,535: null elapsed

hour

0 .. 23

minute

0 .. 59

second

0 .. 59

millisecond

0 .. 999

Measurement

Type Size and Category

Valid Type Range

Type Resolution

Note

Percentage Level

2 bytes (signed long)

–163.840% .. 163.830%

0.005% or 50 ppm

0x7FFF: invalid data

Advertising