Remote-control relay control module sx5l-sbrr081 – IDEC SX5L Series User Manual

Page 29

Advertising
background image

2: H

ARDWARE

S

PECIFICATIONS

2-18

SX5L C

OMMUNICATION

T

ERMINAL

U

SER

S

M

ANUAL

Remote-control Relay Control Module SX5L-SBRR081

General Specifications

Remote-control Relay Control Specifications

Rated Power Voltage

24V AC (50/60Hz) supplied from a remote-control transformer

Power Voltage Range

21.6 to 26.4V AC (including 5% ripple)

Power Consumption

1.8 VA (24V AC) not including power consumption by remote-control relays

Power Inrush Current

15A maximum (24V AC)

Allowable Momentary Power Interruption

10 ms minimum (at the rated power voltage)

Dielectric Strength

1,000V AC, 1 minute between power and FG terminals

Insulation Resistance

100 M

Ω minimum between power and FG terminals (500V DC megger)

Operating Temperature

0 to 55°C (no freezing)

Operating Humidity

30 to 90% RH (non-condensing)

Storage Temperature

–20 to +75°C (no freezing)

Storage Humidity

30 to 90% RH (non-condensing)

Pollution Degree

2 (IEC 60664)

Corrosion Immunity

Atmosphere free from corrosive gases

Altitude

Operation: 0 to 2,000m
Transpor t: 0 to 3,000m

Vibration Resistance

10 to 57 Hz amplitude 0.075 mm, 57 to 150 Hz acceleration 9.8 m/s

2

2 hours per axis on each of three mutually perpendicular axes

Shock Resistance

294 m/s

2

, 11-ms sinusoidal half-wave pulse

Mounting

35-mm-wide DIN rail, direct panel mounting (M4 mounting screws)

Weight (approx.)

250g

Input Points

8 points

Input Type

Feedback input from remote control relays through output signal lines

Output Type

Remote-control relay output

Output Pulse ON Width

100 ms

No. of Common Circuits

1 common circuit for 8 points

Applicable
Devices

Remote-control Relay

BR-12D, BR-22D, BR-1 (Mitsubishi Electric)
WR6165 (Matsushita Electric Works)

Remote-control Transformer

BRT-10B, BRT-20B, BRT-1 (Mitsubishi Electric)
WR2301 (Matsushita Electric Works)

Isolation from Power Line

Photocoupler isolation

Dielectric Strength

500V AC, 1 minute between remote-control relay control and FG terminals

Insulation Resistance

100 M

Ω minimum between remote-control relay control and FG terminals

(500V DC megger)

Advertising