REV 1 EZCT-2000C USER’S MANUAL
99
4.5
Printing Raw Memory Buffer Data
You can print the raw data from the EZCT-2000C’s memory buffer for diagnostic purposes. This
will print a table of current and voltage values stored in the unit’s working memory. To print the
raw buffer data:
a. Start from the “START-UP” menu:
Press the
[2]
key (SETUP).
b. The following screen will be displayed:
Press the
[6]
key (NEXT PAGE).
c. The following screen will be displayed:
Press the
[5]
key (PRINT RAW DATA). The raw buffer data will be printed and you will be
returned to the “START-UP” menu.
1.
SET TIME
2.
SET LANGUAGE
3.
BURIED CT IN DELTA
4.
KNEE POINT MARKER
5.
PRINT RAW DATA
6.
DISABLE H-VTG CHECK
1.
RECORD ID
2.
PRINT RECORD
3.
RECORD DIRECTORY
4.
SAVE/RES RECORD
5.
ERASE RECORD
6. NEXT PAGE
1.
RUN TEST 05/02/13
2.
SETUP 15:14:25
3.
TEST PLANS
4.
DIAGNOSTICS
5.
CURRENT SOURCE