Vanguard EZCT-2000C Plus User Manual
Page 108
Advertising

EZCT-2000C USER’S MANUAL
REV 1
104
5.2
Verifying the EZCT-2000C’s V
x
Sense Circuit Using an External Meter
The excitation voltage (V
x
) sensed by the EZCT-2000C can be verified using an external RMS volt
meter. Follow the steps below to verify the EZCT-2000C’s V
x
sense circuit:
a. Connect the X cables to an RMS volt meter as shown in Figure 26.
b. Select the EZCT-2000C’s Diagnostics mode (see section 5.1).
c. Press the
[∧]
key to raise the V
x
voltage.
d. Verify the V
x
voltage displayed on the EZCT-2000C LCD screen against the value
displayed on the external volt meter.
e. Press the
[STOP]
key to end the test.
Figure 26. EZCT-2000C V
x
Verification Test Connections