Avi recommended exhaust flow rates – XLT XD-9005A User Manual

Page 55

Advertising
background image

55

Technical Support US: 888-443-2751

Technical Support INTL: 316-943-2751

AVI RECOMMENDED EXHAUST FLOW RATES

Top Middle Bottom

187.5

187.5

93.75

93.75

[57.15]

[57.15]

[28.58]

[28.58]

187.5

187.5

93.75

93.75

[57.15]

[57.15]

[28.58]

[28.58]

189.75

241.5

155.25

181.125

[57.84]

[73.61]

[47.32]

[55.21]

189.75

241.5

155.25

181.125

[57.84]

[73.61]

[47.32]

[55.21]

187.5

187.5

93.75

93.75

[57.15]

[57.15]

[28.58]

[28.58]

189.75

241.5

155.25

181.125

[57.84]

[73.61]

[47.32]

[55.21]

287.25

365.625

235.125

274.3125

[87.55]

[111.44]

[71.67]

[83.61]

189.75

241.5

155.25

181.125

[57.84]

[73.61]

[47.32]

[55.21]

287.25

365.625

235.125

274.3125

[87.55]

[111.44]

[71.67]

[83.61]

287.25

365.625

235.125

274.3125

[87.55]

[111.44]

[71.67]

[83.61]

287.25

365.625

235.125

274.3125

[87.55]

[111.44]

[71.67]

[83.61]

Exhaust Flow Rates VELOCITY (min. recommended)

Switches On

18xx

24xx

32xx

38xx

Single

X

Double

X

X

X

X

Triple

X

X

X

X

X

X

NOTE: All values are FPM [M/Min] unless otherwise noted.

NOTE: Figures represent VELOCITY measured at the Grease Filter.

X

X

X

X

X

X

NOTE: Most building codes require 500 Feet per Minute velocity. Exhaust duct is 1 ft

2

. Check

with your local building official for requirements.

The VELOCITY readings above are obtained by holding an anemometer 3” away from the Grease
Filter. Take several readings in different locations across the filters and average the results.