Learn the configuration menu, Configuration menu; learn, Configuration overview – Watlow Series 935A User Manual

Page 18

Advertising
background image

1 6

Watlow Series 935A User’s Manual

The Configuration Menu is the second sub-menu in the Operations Menu. Use it to set Inputs, Ranges, Output Types, Alarms, Timer,
Failure Mode, and Lockouts.

To go to the Configuration Menu:

1.

Go first to the Operations Menu by pressing

.

and

,

simultaneously for three seconds.

2.

Scroll through the Operations Menu with

,

until you see the

[CnFg]

prompt.

3.

While holding

ß

to display

[``no]

, choose

[`YES]

with

.

or

,

.

4.

Release

ß

to see the first

[CnFg]

prompt,

[``In]

.

5.

To leave the Configuration Menu, press

.

and

,

for 3 seconds.

Table 6 - Configuration Menu Overview

Input Type - Choose sensor type. See p. 21 for sensor ranges.

[```J]

[```H]

[```t]

[```n]

[```E]

[```S]

[`rtd]

[`r†d]

J t/c

K t/c

T t/c

N t/c

E t/c

S t/c

1.0° RTD

0.1° RTD

Celsius/Fahrenheit - Choose displayed unit of measure.

[``°F]

[``°C]

°F

°C

Input Range Low - Select lowest displayable set point. Ranges, p. 21.

[``In]

[``rh]

Select a value (lowest displayable set point) between
Input Type Range Low and Input Range High.

Input Range High - Select highest displayable set point. Ranges, p. 21.

[``Rl

[``In]]

Select a value (highest displayable set point) between
Input Type Range High and Input Range Low.

Output 1 Function - Choose Output 1 type; see Valid Outputs Table, p. 21.

[hEAt]

[COOL]

[ALM]

[`rSP]

[`FPL]]

[nonE]]

Heat

Cool

Alarm

Remote

Front

None

Set Point

Panel Lock

Output 2 Function - Choose Output 2 type (dependent on Output 1 choice).

hEAt]

[COOL]

[ALM]

[thM]

[tMS]

[nonE]]

Heat

Cool

Alarm

Timer

Timer

None

Hr./Min.

Min./Sec

Display Default - Choose the primary (last 2 characters) and secondary (first 2 characters) default displays. Press

ß

to toggle to the secondary display

for 15 seconds.

[``Ac]

[AcSP]

[Acti]

[tiAc]

[tiSP]

No

Actual

Actual

Time

Time remaining

secondary

temp.

temp.

remaining

Set point temperature

Actual

Set point

Time

Actual

temp.

temp.

remaining

temp.

Alarm Type - Choose alarm type with output action.

[Prnc]

[Prno]

[dEnc]

[dEno]

Process

Process

Deviation

Deviation

normally

normally

normally

normally

closed

open

closed

open

[``In]

[`C_F]

[``rL]

[``rh]

[`Ot1]

[`Ot2]

[dISP]

[ALty]

Learn the Configuration Menu