Calibrating the 935a, Calibrating, Tc50 – Watlow Series 935A User Manual

Page 36: Tc00, R`15, R380

Advertising
background image

3 4

Watlow Series 935A User’s Manual

Calibrating the 935A

Calibration requires a precision millivolt source with
thermocouple compensation, an adjustable 0-10 volt source,
and a decade resistance box.

[tr50]

and

[tr00]

calibrate the thermocouple span.

[``tc]

calibrates the ambient compensation.

[r380]

and

[r`15]

calibrate the RTD span.

• 0V is required when calibrating

[tc00]

and

[r`15]

for remote set point calibration.

• 5V is required when calibrating

[tc50]

and

[r380]

for remote set point calibration.

• When calibrating, calibrate all points for consistency in results.
• Allow the unit to warm up for 15 minutes before calibrating.

Quick Calibration
Restore:

Press all three keys
simultaneously until

[tc50]

appears in the

display, press

.

once and

[`rSt]

will

appear in the display.
Press and hold

ß

,

the display will show

[``no]

, press

.

to

change display to

[`YES]

. Press and

hold

.

and

,

for 3 seconds to exit
the

[`CAL]

menu.

NOTE: Restore
Factory Calibration

[`rSt]

=

[`YES]

restores factory
calibration
values to all
calibration prompts.

Figure 8a -
Thermocouple Calibration

Figure 8b -
RTD Calibration

Calibration Menu

[tc50]

tc50

[tc00]

tc00

[``tc]

tc

[r`15]

r15

[r380]

r380

[`rSt]

rst

mV source = 50.000mV
Volt source = 5V

mV source = 0.000mV
Volt source = 0V

mV source = Temp. Compensation
Volt source = 0V

Decade Box = 15.00 ohms
Volt source = 0V

mV source = 380.00 ohms
Volt source = 5V

• Store TC counts at 50.000mV
• Store 5V remote set point
counts for use with TC

• Store ambient counts
at 32

°

F. Type J.

• Store low end RTD counts
• Store 0V remote set point
counts for use with RTD

• Store high end RTD counts
• Store 5V remote set point
counts for use with RTD

• Restore factory calibration

mV

source

Volt

source

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

Decade

Box

Volt

source

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

• Store TC counts at 0.000mV
• Store 0V remote set point
counts for use with TC

Advertising