Set up remote set point input, Remote set point, Remote set point wiring – Watlow Series 935A User Manual

Page 24

Advertising
background image

2 2

Watlow Series 935A User’s Manual

To Set Up Remote Set Point…

1.

Wire the control per the example below and the information on p. 42-45.

2.

Go to

[CnfG]

, make

[`in]

and

[`c_f]

choices, then

3.

Make

[``In]

and

[`C_F]

choices, then

4.

Scale the 0-5V

Î

(dc) input with

[``rL]

and

[``rh]

.

5.

Go to

[`Ot1]

, and choose

[`rSP]

.

6.

Go to the Operations Menu;

[`L-r]

, choose

[```r]

.

Output 1

[`Ot1]

[`rSP]

Select Remote Set Point for Output 1

Local / Remote

[`L-r]

[```L]

Local set point active

[```r]

Remote set point active

Remote Set Point is scaled by

[``rh]

and

[``rL]

.

0V input results in a set point of

[``rL]

.

5V input results in a set point of

[``rh]

.

Adjust

[``rL]

and

[``rh]

to match your input to desired set point adjustment.

The Remote Set Point will display instead of Primary Set Point.

Auto-tune always uses the Primary Set Point.

Deviation Alarm uses the active Set Point.

Figure 5 - Remote Set Point Wiring

See p. 42-45 for more wiring information.

NOTE: Sensor required on Terminals 1 and 2.

WARNING: All wiring and fusing must conform to local and national electric codes.
Contact local authorities for further information. Failure to comply with electric codes
could result in injury or death, or damage to property.

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

Configuration Menu

[``In]

Input Type

[`C-F]

Celsius/Fahrenheit

[``rL]

Input Range Low

[``rh]

Input Range High

[`Ot1]

Output 1 Function

[`Ot2]

Output 2 Function

[dISP]

Display Default

[FAIL]

Failure Mode

[SLOC]

Set Point Lockout

[`TAG]

Lockout Tag

Operations
Menu

[`Aut]

Auto-tune

[`L-r]

Local / Remote

[`Pid]

PID

[CnFG]

Configuration

Set Up Remote Set Point Input