Learning alarms, Alarms; learn – Watlow Series 935A User Manual

Page 26

Advertising
background image

2 4

Watlow Series 935A User’s Manual

Configuration Menu

[``In]

Input Type

[`C_F]

Celsius/Fahrenheit

[``rL]

Input Range Low

[``rh]

Input Range High

[`Ot1]

Output 1 Function

[`Ot2]

Output 2 Function

[dISP]

Display Default

[ALtY]

✓

Alarm Type

[AhYS]

✓

Alarm Hysteresis

[`LAt]

✓

Alarm Latch

[`SIL]

✓

Alarm Silencing

[FAIL]

Failure Mode

Operations
Menu

[`Aut]

Auto-tune

[`ALO]

✓

Alarm Range Low

[`AhI]

✓

Alarm Range High

[`Pid]

PID

[CnFG]

Configuration

Learning Alarms

Alarms signal an excursion from normal operating conditions. In general, audible alarms or lights

connected to alarm outputs will signal a problem. In the 935A the front panel LED “1” or “2” indicates an
alarm with

[``hI]

or

[``LO]

flashing on the main display.

•

Process alarms use absolute high and low values to trigger an alarm. Use this alarm type if your
process may be subject to temperatures that it must not exceed. Use

[`AhI]

and

[`ALO]

to set

alarm points at or near these values. See Table 10:

[ALtY]

, next page.

•

Deviation alarms are triggered by a deviation from the set point. The alarm high value

[`AhI]

is

the deviation above set point, and the low value

[`ALO]

is the deviation below set point. Whenever

the set point is adjusted, the alarm settings are relative to that value. Deviation alarms use the cur-
rently controlling set point, whether primary, remote, idle, or 90% of primary, during auto-tuning. See
Table 10:

[ALtY]

, next page.

•

Normally Open,

[dEno]

or

[Prno]

, Alarms energize the alarm output when an alarm condition

occurs, and de-energize it when cleared. Use this type to activate external devices such as audible
alarms or lights. See Table 10:

[ALtY]

, next page.

•

Normally Closed,

[dEnc]

or

[Prnc]

, Alarms de-energize the alarm output when an alarm condi-

tion occurs, and energize it when the alarm is cleared. Use this type as a “deadman” switch where
system continuity is required for operation. See Table 10:

[ALtY]

, next page.

For example, by running the control output through the alarm output, you can set a normally
closed process alarm to disable the process when the process exceeds the alarm set point.
The alarm output will be off when power is off.

•

Alarm Hysteresis sets a point the process must pass on a return (from an alarm condition excur-
sion) to the

[`ALO]

and

[`AhI]

points before the alarm can clear. This prevents the alarm output

from “chattering” if the process is hovering around the alarm set point. See Table 10:

[AhYS]

, next

page.

•

Latching Alarms require the operator to clear them with a ß press after the process returns to a
safe, or non-alarm condition. Non-latching alarms self-clear. See Table 11:

[`LAt]

, p. 27.

•

Silenced Alarms provide a means to clear the alarm output with a

ß

press even if the alarm

condition still exists. The flashing

[``hI

] or

[``LO]

message will persist until the alarm condition

ceases. See Table 11:

[`SIL]

, p. 27. If

[`SIL]

=

[`YES]

, alarms are disabled (no message or

output) on startup until the safe area is reached.

•

Alarm High and Low Points,

[`AhI]

and

[`ALO]

, in the Operations menu determine where

alarms will trigger. Alarm hysteresis

[AhYS]

determines where an alarm condition clears. See Table

11, page 27.

•

To Clear an Alarm that is latched or “silence-able’ requires the operator to press the

ß

key after

the process returns to a safe, or non-alarm condition. Non-latching alarms self-clear. See Table 11:

[`LAt]

and

[`SIL]

, p. 27.

Table 10 (p. 25) and Table 11 (p. 27) illustrate the Series 935A alarm features.

Advertising