Watlow Series 935A User’s Manual

3 7

To Troubleshoot Sensor
• Remove sensor wires from Terminals 1 and 2.

• For a thermocouple sensor Series 935A, place a jumper wire on Terminals 1 and 2.

Control should display the ambient temperature at the back of the control.

• For an RTD sensor Series 935A, place a 110 +/- 10

resistor on Terminals 1 and 2.

The control should read 100

= 32°F, 110

= 77°F, 120

= 127°F.

• An RTD sensor Series 935A can be configured in software as if it were a

thermocouple unit, and then tested as above.

• You can restore factory calibration

[`rST]

, see p. 34-35.

Table 13 - Error Codes and Actions

Display

Probable Cause

Recommended Action

Reversed thermocouple

Change the sensor

A-D

connection + to –.

leads on Terminals 1 and 2.

under flow

Sensor type

Go to In prompt, check selection (see p. 20),

Sensor

mismatch or open RTD.

or check RTD, replace as necessary.

under range

Sensor type

Go to In prompt,

Sensor

mismatch.

check selection (see p. 20).

over range

Open Thermocouple, bad

Check the sensor,

A-D

connection, or broken wire.

replace as necessary.

over flow

Electrical noise.

Cycle power to system. See if error clears.
Check system for electrical interference.

Control is inoperable.

Check for line voltage at
terminals 7 and 8.

Table 14 - Troubleshoot Control Outputs

When indications such as significant differences between set point and
actual temperatures point to no output action, check output configurations
as described on p. 23. Check wiring, p. 44.

Measure

Output

Terminals

Load-on State

Load-off State

“C” Output 1

3 & 4

LED 1 on

LED 1 off

3.0 to 7.0V

Î

(dc)

0.0V

Î

(dc)

“C” Output 2

5 & 6

LED 2 on

LED 2 off

3.0 to 7.0V

Î

(dc)

0.0V

Î

(dc)

“D” Output 2

5 & 6

LED 2 on

LED 2 off

0V

Î

(dc)

line voltage.

Load sees line voltage

Load sees 0V

Î

(dc)

“K” Output 2

5 & 6

LED 2 on

LED 2 off

<2V

Î

(dc)

line voltage

Load sees line voltage

Load sees 0V

Î

(dc)

[`Er1]

[`Er2]

[`Er3]

[`Er4]

[`Er5]

[````]