Specifications, Specifications 50 – Watlow Series 935A User Manual

Page 52

Advertising
background image

5 0

Watlow Series 935A User’s Manual

Specifications

Specifications (2191)

Control Mode

• Auto-tune PID.
• PID, PD, PI, on/off.
• Countdown timer; hours:minutes, minutes:seconds.
• Timer output modes; Delay-off, Delay-on, Signal-off, Signal-on.

Agency Approvals

• UL/C-UL 508 Listed, File #E102269.
• IP65/NEMA 4X

2

rated front panel.

• CE approved:

•89/336/EEC Electromagnetic Compatibility Directive:
EN61326 Industrial Immunity, Class A Emissions
•73/23/EEC Low-voltage Directive:
EN 61010-1: 1993 Safety.

Operator Interface

• Single, seven-segment digital display, factory selectable red or green.
• Outputs/operation annunciators, three discrete LEDs.
• Three tactile feedback momentary switches.
• Front panel lock dry contact closure disables front panel operation.

Accuracy

• ±0.25% of span, ± 1 LSD, or
• Types S and T thermocouple @ < 200°C, ±0.32% of span, ± 1 LSD,

typical.

Ambient Rejection

• < 0.15°C/°C rise in ambient, or
• Types S and T thermocouple, @ < 0.47°C/°C rise in ambient typical.

Sensors/Inputs

• Sensor input sampling rate: 10 samples/second (10Hz).
• Type E, J, K, N, S and T thermocouple, grounded or ungrounded

junction.

• RTD, 100

platinum two-wire , DIN curve

• Remote set point input, field-selectable,

0-5V

Î

(dc), scalable, 10k

input impedance. (Remote Input Option A

only.)

• Remote timer start dry contact closure initiates timer start. (Remote

Input Option B only.)

Input Range

Specified temperature ranges represent the controller’s operational
span.

Thermocouple

Type E

-200

to

799°C

(-328

to

1470°F)

Type J

0

to

750°C

(32

to

1382°F)

Type K

-200

to

1250°C

(-328

to

2282°F)

Type N

0

to

1250°C

(32

to

2282°F)

Type S

0

to

1450°C

(32

to

2642°F)

Type T

-200

to

350°C

(-328

to

662°F)

RTD Resolution Platinum 0.00385 Curve

-200

to

700°C

(-328

to

1292°F)

0.1°

-128.8

to

537.7°C

(-199.9

to

999.9°F)

Control Output

• Output update rate: 1/second (1Hz).

1 Output/Remote Input

• Switched dc logic signal, 6V

Î

(dc) @ 60mA nominal, short circuit pro-

tected, non-isolated. (Watlow DIN-a-mite® power controller
compatible).

2 Output

• Switched dc logic signal, 6V

Î

(dc) @ 60mA nominal, short circuit pro-

tected, non-isolated (Watlow DIN-a-mite® power controller compatible).

• Electromechanical

1

relay, Form A, 2A @ 30V

Î

(dc) or, 240V~ (ac), with-

out contact suppression

3

. (Remote Input Option A only.)

• Solid-state relay, Form A, 0.5A, 24 to 264V~ (ac), without contact

suppression

3

. Off-state output impedance 31M

. (Remote Input Option

A only.)

Output Cycle Time

• Switched dc and solid-state relay; 5.0 second default, 0.1 second

minimum.

• Electromechanical relay; 30.0 second default, 5.0 second minimum.

Line Voltage/Power

• 100-240V~ (ac) +10%, -15%; (85-264V~ [ac]) 50/60Hz, ±5%.
• 24-28V

ı

(ac/dc) +10%, -15%; (20-31V

ı

[ac/dc]) 50/60Hz, ±5%.

(Remote Input Option A only.)

• Fused internally (factory replaceable only) time-lag type, 2A, 250V.
• Power consumption 6VA maximum.
• Data retention upon power failure via non-volatile memory.
• Switching supply speed 45kHz, ±5kHz.

Operating Environment

• 0 to 65°C (32 to 149°F).
• 0 to 90% RH, non-condensing.

Storage Temperature

• -40 to 85°C (-40 to 185°F).

Terminals
• Touch-safe set screw type, accepts 0.5 to 4mm

2

(22 to 12 AWG

wire). Torque to 0.1 Nm (4.5 in lbs).

Controller Weight

• 113 g (4.0 oz).

Shipping Weight

• 207 g (7.3 oz).

These specifications are subject to change without prior notice.