Output 2 wiring output 1 wiring, Internal circuitry – Watlow Series 935A User Manual

Page 45

Advertising
background image

Watlow Series 935A User’s Manual

4 3

WARNING: All electrical wiring and fusing must conform to local and national electric codes. Contact local authorities for
further information. Failure to comply with electric codes could result in injury or death, or damage to property.

ç

CAUTION: Failure to install a 60 to 70

, 0.5w resistor across the customer-supplied Front Panel Lock switch will cause the

panel to lock out even when the switch is open. Injury to personnel, or damage to equipment or property could result.

WARNING: When Output 1 is a Front Panel Lock

[`Ot1]

=

[`FPL]

,

the output is energized! Do not connect a power switching

device to Output 1; injury or death, or damage to equipment or property could result.

NOTE:
Switching inductive loads (relay coils, solenoids, etc.) with the mechanical relay or solid-state relay output options
requires using an R.C. suppressor. Watlow carries the R.C. suppressor Quencharc brand name, which is a trademark of
ITW Pakron. Watlow Part No. 0804-0147-0000.

Output 1; Front Panel Lock

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

60 to 70

, 0.5w resistor

Output 2; Solid State Relay; "K"

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

Output 2; Electromechanical Relay; "D"

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

Power

Output 2; Switched DC; "C"

S2


1

S1

+
2


3

+
4


5

+

6

7

8

OT1

IN

OT2

POWER

Internal Circuitry

+5.7 to 8V

Current

Limit

60mA

Output 1; Switched DC; "C"

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

Internal Circuitry

+5.7 to 8V

Current

Limit

60mA

Output 2 Wiring

Output 1 Wiring

See Caution

Advertising