Fine tune the pid settings, Pid fine tuning – Watlow Series 935A User Manual

Page 35

Advertising
background image

Watlow Series 935A User’s Manual

3 3

Fine Tune the PID Settings

1. Set

[Pb`h]

and

[Ct`h]

in degrees.

2. If Proportional Band Heat

[Pb`h]

= 0, Set Hysteresis Heat

[HySh]

. The Series 935A will provide on/off

control with the hysteresis value selected, and no proportioning action.

3. Proportional Bands should be decreased for tighter control but increased to eliminate oscillations.

4. Cycle Time Heat

[Ct`h]

is limited to a minimum of 5.0 seconds for the electromechanical relay to help

reduce wear. The electromechanical relay (D, Output 2) is not recommended for PID control. It is war-
ranted to 100,000 contact closures only. Alarm or on/off control are appropriate applications for the
Series 935A's electromechanical relay output.

5. Set Dead Band

[``db]

to adjust the effective cool set point above the primary set point by the dead

band value in degrees. In cool/heat applications, dead band prevents continuous cool output action by
creating a buffer between heating and cooling output action.

6. Set

[Pb`c]

and

[Ct`c]

in degrees.

7. If Proportional Band Cool

[Pb`c]

= 0, Set Hysteresis Heat

[HYSc]

. The Series 935A will provide on/off

control with the hysteresis value selected, and no proportioning action.

8. Proportional Bands should be decreased for tighter control but increased to eliminate oscillations.

9. Cycle Time Heat

[Ct`h]

is limited to a minimum of 5.0 seconds for the electromechanical relay to help

reduce wear. The electromechanical relay (D, Output 2) is not recommended for PID control. It is war-
ranted to 100,000 contact closures only. Alarm or on/off control are appropriate applications for the
Series 935A's electromechanical relay output.

10. Set Integral

[``It]

to eliminate droop in the system. Lower the value for more droop reduction.

Adjustable from 0 to 99.9 minutes / repeat.

11. Set Derivative

[``dE]

to prevent overshoot. Increasing the value slows the approach to set point.

Adjustable from 0 to 9.99 minutes.

12. Calibration Offset

[`Cal]

eliminates the difference between the displayed process temperature and the

actual process temperature value.

PID Menu

Set up Heat:

[Pb`h]

Proportional Band

[hySh]

Hysteresis

[Ct`h]

Cycle Time

[``db]

Dead Band

Set up Cool:

[Pb`c]

Proportional Band

[hySc]

Hysteresis

[Ct`c]

Cycle Time

Set up General:

[``It]

Integral

[``dE]

Derivative

[`CAL]

Calibration Offset