2 3

To Set Up Front Panel Lock…

1.

Install an external switch.

2.

Wire the control per the example below and the information on p. 42-45.

3.

Go to

[CnFG]

, then

[`Ot1]

, and choose

[`FPL]

.

Table 9 - Using Front Panel Lock

Figure 6 - Front Panel Lock Wiring

See p. 43 for more wiring information.

(Closed switch = locked)

WARNING: When Output 1 is a Front Panel Lock

[`Ot1]

=

[`FPL]

, the output is energized! Do

not connect a power switching device to Output 1; injury or death, or damage to equipment or
property could result.

ç

CAUTION: Failure to install a 60 to 70

, 0.5 watt resistor across the customer-supplied Front

Panel Lock switch will cause the panel to lock out even when the switch is open. Injury to
personnel, or damage to equipment or property could result.

Output 1; Front Panel Lock

S2


1

S1

+
2


3

+
4

5

6

7

8

OT1

IN

OT2

POWER

60 to 70

0.5w resistor See Caution

Configuration Menu

[``In]

Input Type

[`C_F]

Celsius/Fahrenheit

[``rL]

Input Range Low

[``rh]

Input Range High

[`Ot1]

Output 1 Function

[`Ot2]

Output 2 Function

[dISP]

Display Default

[FAIL]

Failure Mode

[tIM

Timer Function

[Strt]

Start Timer

[`rdY]

Timer Ready Band

[``St]

Signal Time

[SLOC]

Set Point Lockout

[`tAG]

Lockout Tag

[`Ot1]

[`FPL]

Set Up Front Panel Lockout

[`Ot1]

=

[`FPL]

View Process

Yes

View Set Point

Yes

Change Set Point

No

Auto-tune

No

Reset Alarm

Yes

View or Change Operation

No

Menu (Except Config. Menu)
View or Change Configuration

No

Menu (Except Tag)
View or Change PID Menu

No

RDY

2

1

SET

[`fpl]

Advertising