Input scaling example: 0 to 5 vdc sensor, Input scaling example: 0 to 5 vdc sensor 90, Table 4.4—input readings 90 – Watlow Series D8 User Manual

Page 108: Table 4.5—scaling values 90

Advertising
background image

Chapter 4: Operation and Setup

Series D8 User’s Guide

90

Watlow Anafaze

Doc. 0600-3120-2000

Input signal high

= 20 mA/20 mA = 1.0 = 100%

For the Input range low and Input range high parameters,

enter the process values that correspond to the low and

high signals. In this case, a 20 percent (4 mA) signal rep-

resents 0.0 PSI. A 100 percent (20 mA) signal represents

50.0 PSI.

Table 4.4

Input Readings

Table 4.5

Scaling Values

Input Scaling Example: 0 to 5 Vdc Sensor

Situation

A flow sensor connected to the controller measures the flow

in a pipe. The sensor generates a 0 to 5 Vdc signal. Indepen-

dent calibration measurements of the flow in the pipe indicate

that the sensor generates 0.5 V at 3 gallons per minute (GPM)

and 4.75 V at 65 GPM. The calibration instrument is accurate

±1 GPM.

Setup

For the Disp format parameter in the Input menu, choose
-999to 3000

, because the calibrating instrument is precise to

±1 GPM.
The tables below show the minimum and maximum input sig-

nals and their corresponding process variables, and the result-

ing values for the scaling parameters.

Process
Variable

Displayed

Sensor

Input

Reading in

Percent of Full Scale

50.0 PSI

20 mA

100%

.0 PSI

4 mA

100% x (4 mA/20 mA) = 20%

Parameter

Value

Input range high

50.0 PSI

Input high signal

100.0%

Input range low

.0 PSI

Input low signal

20.0%