Watlow Series D8 User Manual
Page 127

Series D8 User’s Guide
Chapter 4: Operation and Setup
Doc. 0600-3120-2000
Watlow Anafaze
109
Table 4.14
Parameter Settings for the Ratio
Loop (Loop 2) in the Example
To complete the setup, loop 2 must be configured for inputs,
outputs, and alarms. In addition, loop 1 may be configured for
outputs and alarms.
Menu
Parameter
Value
Comment
Ratio
Ratio master loop
01
Loop 1 is the master loop (receives the input
signal from the external device).
Ratio
Ratio low SP
0˚F
For this example, we will assume that the pro-
cess can be set safely over the entire range of
0 to 300° F. If desired, we could set a more
restrictive range for the ratio loop.
Ratio
Ratio high SP
300˚F
Ratio
Control ratio
1.0
For this example, we want to retain the origi-
nal input value, so we will multiply it times 1.0.
Ratio
Ratio SP diff
0
For this example, we want to retain the origi-
nal value, so we will add 0.