Proportional-Only Control on the Primary Loop

The PID parameters of the primary loop must be tuned to pro-

duce the desired effect on the set point of the secondary loop.

The primary loop typically uses proportional-only control.

Disabling the integral and derivative components of PID

makes the secondary set point a predictable function of the

primary loop’s process variable.
The proportional band is selected so that the set point of the

secondary loop has the desired relationship to the process

variable of the primary loop. For an example, see Cascade

Control Example: Water Tank on page 102.

Set Point of Secondary Loop

(Engineering Units)

High Set Point

Low Set Point

-100%

Output of Primary Loop (Percent of Full Scale)

100%

Set Point of the Secondary Loop

(Engineering Units)

High Set Point

Low Set Point

0%

Output of Primary Loop (Percent of Full Scale)

100%