Chapter 6: Menu and Parameter Reference

Series D8 User’s Guide

126

Watlow Anafaze

Doc. 0600-3120-2000

If you have enabled remote job selection (see BCD Job Load

on page 126), you will see the message below, and you will

not be able to use the controller keypad to save a job.

Values:

1 to 8 (1 to 8) or none (0). Values in parentheses are

for communications.
Default:

none (0)

DeviceNet Object:

Global (6B hex)

BCD Job Load

Choose the digital input(s) to use for remote job selection. The

controller uses the states of the selected inputs as a binary

code that specifies which job number to run (see Table 6.3).
To save jobs into memory, use the Save setup as job parame-

ter.

Values:

See Table 6.3

Default:

disabled (0)

DeviceNet Object

: Global (6B hex)

Table 6.3

Values for BCD Job Load

BCD Job Load Logic

Choose which state is considered “true” for the digital inputs

that are used for remote job selection.

If 1=true is selected, then an input is true if connected to

controller common, and false for an open circuit.

If 0=true is selected, then an input is true for an open cir-

cuit, and false if connected to controller common.

Table 6.4 shows which combinations of input states are re-

quired to load each job.

Display

Value

DeviceNet

Value

Description

use D/I 1

1

Use digital input 1 for remote selection of jobs 1 and 2.

use D/I 1-2

2

Use digital inputs 1 and 2 for remote selection of jobs 1 to 4.

use D/I 1-3

3

Use digital inputs 1 to 3 for remote selection of jobs 1 to 8.

disabled

0

Disable remote job selection

lSave setup as r
not available

lBCD job load r
bdisabled

lBCD job load r
logic b1=true