Figure 7.4
Input Circuit
Current Inputs
For each current input, you must install a resistor. The value
of the resistor must be correct for the expected input range. In-
stall the resistor in the listed resistor pack (RP) location. Note
the resistor pack locations have three through-holes. Install
the resistor as shown in the illustration below.
Table 7.5
Resistor Values for Current Inputs
Resistor tolerance:
±
0.1%
Table 7.6
Resistor Locations for Current In-
puts
Input Range
Resistor Value RD
0 to 10 mA
6.0
Ω
0 to 20 mA
3.0
Ω
Loop
Resistor
Location RD
Loop
Resistor
Location RD
1
RP1
5
RP5
2
RP2
6
RP6
3
RP3
7
RP7
4
RP4
8
RP8
Com
IN-
RC (RTD)
IN+
RD
RP
Analog
Input
Terminal
Internal
RP
+5 Vdc
Reference
To D8
Circuitry
RC (Voltage)
+
-
RP#
RD