Yokogawa 415 Steam and Gas User Manual

Page 13

Advertising
background image

4-20mA Inputs

Inputs:

Flow (2), pressure & temperature.

Input Impedance:

250 ohms.

Measurement Ranges:

Pressure: 0kPa (abs) (0 psia) to 100,000 kPa

(10,000 psia).

Temp:-273°C (-459.4°F) to 1200°C (2192°F).

Accuracy:

0.05%

Circuit:

The 250 ohm resistors are connected to a
common signal ground (current sinking).

Span (Flow):

999,999.

RTD Input (Model 415R)

Temperature
Measurement Range:

-100°C (-148°F) to 200°C (392°F),
Note: a wider temperature range can be
handled via a 4-20mA input.

Accuracy:

0.1°C

RTD Type:

Platinum PT100.

Linearity:

The non-linearity of the RTD is internally
compensated for.

Pressure Input

Type:

Absolute or Gauge.

Span:

The absolute or gauge pressure at both 4mA
and 20mA is programmable.

Atmospheric:

If a gauge pressure sensor is used the
atmospheric pressure can be programmed.

4-20mA Output

Function:

The flowrate selected as the Default display
is output on the 4-20mA output.

Resolution:

10 bits.

Accuracy:

Better than 0.1%.

Maximum Load:

500 ohms internally powered.
950 ohms from 24 VDC.

Isolation:

Output is isolated.

Specification 11