PROGRAMMING THE SPAN AS MASS

It is also possible to enter the span of an analog flowmeter in mass
(instead of volume) at a nominal flowrate. The flow computer will
then automatically calculate the Span, S

VB

, for corrected volume flow

as:

......(9)

S

VB

=

S

M

ρ

B

Example 2

If a flowmeter produces 1000 kg/h at 30°C and 220 kPa, and the
specific gravity is 1.52 then from equation (2)

ρ

=

3.4834 x 1.52 x 220

1 x

(

30 + 273.2

)

(assuming Z

B

= 1)

= 3.84 kg/m

3

Therefore, from equation (9)

S

VB

=

1000

3.84

If the span is programmed as mass S

M

= 1000 kg/hr, with the base

temperature programmed to 30°C and the base pressure
programmed to 220 kPa, then the flow computer will display both
mass (kg/hr) and volume (m

3

/hr) corrected to a base condition of

30°C and 220 kPa.

20 Operation

= 260 m

3

/hr