Yokogawa 415 Steam and Gas User Manual

Page 75

Advertising
background image

7.2 WIRING DESIGNATIONS FOR THE MODEL 415

Terminal

Model 415R

Model 415A

1

Calibration Link

Calibration Link

2

Signal Ground

Signal Ground

3

Flow 1 (4-20mA)

Flow 1 (4-20mA)

4

PT100 I (+)

Temperature (4-20mA)

5

PT100 Signal (+)

Reset Switch

6

PT100 Signal (-)

Display Switch

7

Pressure (4-20mA)

Pressure (4-20mA)

8

Flow Common (-)

Flow Common (-)

9

Flow Pulse Input (+)

Flow Pulse Input (+)

10

Pulse Out

Pulse Out

11

DC Power Out (8-24V)

DC Power Out (8-24V)

12

DC Ground

DC Ground

13

DC Power Input

DC Power Input

14

PT100 I (-)

Flow 2 (4-20mA)

Note:

When using a single 4-20mA flowmeter, it is connected to

terminal 3. The second 4-20mA flow input on terminal 14 is only
used when there are dual 4-20mA inputs. In this case, terminal 3
becomes the High Flow input and terminal 14 is used for the low
flow.

Terminal

Analog Flow Output (4-20mA)

RS232/422/485

20

Not To Be Used

RS232 Signal Ground

21

0 Volts

RS232 Data In

22

0-10 Volts

RS232 Data Out

23

-12 Volts

RS422/485 (-) Data Out

24

I(-)

RS422/485 (+) Data Out

25

I(+)

RS422/485 (-) Data In

26

+15 Volts

RS422/485 (+) Data In

27

Not To Be Used

RS232 CTS

Installation 73