Yokogawa 415 Steam and Gas User Manual

Page 21

Advertising
background image

Example 1

Flow is to be measured across an orifice in the range of 0 - 2000
scm/hr. Because flow needs to be measured over a 10:1 range, two
transmitters are spanned as follows:

Transmitter 2

0 - 600 scm/hr

Transmitter 1

0 - 2000 scm/hr

Hence, above 600 scm/hr, transmitter 2 is used and below 600
scm/hr, transmitter 1 is used. Since D. P. transmitters are accurate
over a 3:1 range, then the system will provide reliable readings
between 200 to 2000 scm/hr, which is a 10:1 turndown.

Both transmitters will be individually scaled to equations 5 & 6 or
7 & 8, as appropriate.

PROGRAMMING THE FLOW COMPUTER

For equations 4 to 8 to work correctly, a number of parameters need to
be programmed:

K

F

K-factor (for frequency producing flowmeters)

S

VB

(or S

M

) Span (for analog flowmeters)

T

B

Base temperature

P

B

Base pressure

G

Specific Gravity of Gas

The flow computer will measure the flow input A (normalised between
0 and 1), the temperature, T

F

, and pressure, P

B

. Depending on the gas

equation selected, the compressibility factors and density are then
calculated. Other parameters must also be programmed and these are
fully detailed in section 5.

Operation 19