Dnp object implementation table, Dnp3 – Yokogawa Standalone MW100 User Manual
Page 128

-
128/131 -
IM MW100-S16E-1
Ed01
3.2. DNP object implementation table
DNP object implementation table of DNP slave/server function in MW100 is shown
in Table 72 to Table 75.
Table 72. DNP object implementation table (1/4)
DNP3
OBJECT IMPLEMENTATION TABLE
OBJECT
REQUEST
RESPONSE
Grp. Var.
Description
Function
Code
Qualifier
Code
Function
Code
Qualifier
Code
1
0
Binary Input
1
00, 01, 02
06
129
00, 01, 02
1
Binary
Input
packed format
2
Binary
Input
with Flag
2
0
Binary Input Event
1
06, 07, 08
129
130
17, 27
1
Binary
Input
Event
without Time
2
Binary
Input
Event
with Time
3
Binary
Input
Event
with Relative Time
10
0
Binary Output
1
00, 01, 02
06
129
00, 01, 02
1
Binary
Output
packed format
2
Binary
Output
with Flag
11
0
Binary Output Event
1
06, 07, 08
129
130
17, 27
1
Binary Output Event
without Time
2
Binary Output Event
with Time
12
1
Control Relay Output Block
(CROB)
3, 4, 5, 6
17, 27
129
echo back
of request
2
Pattern Control Block
3
Pattern
Mask