Example of the object table configuration is shown in Figure 26. Only the mapped
channel data in this table become accessible from DNP master/client.
Figure 26. Example of object table configuration
:
Analog
Input
(
30)
Analog
Input Event
(
32)
Class 1 Event
Class 2 Event
Class 3 Event
- Only three channels begin from 011 are mapped to the object
- Exception occurred in the object are reported as Class 1 event
- Default variation of the object data is 1 (Integer 32)
- Destination is Analog Input (30) and their indices are 10 to 12
CH 001
:
Screen of DNP 3.0 object setting
CH 010
CH 011
CH 012
CH 013
CH 014
CH 060
0
:
9
10
11
12
13
:
59