Yokogawa Standalone MW100 User Manual
Page 80

-
80/131 -
IM MW100-S16E-1
Ed01
Table 38. Parameter for configuring command table of DNP master
Kind
Configuration
Function
Publishing function codes for accessing DNP objects
- selectable from “Off”, “Poll”, “Read”, “Select + Operate”,
“Direct Operate”, “Direct Operate, NR”
Slave
Table number of the destination
- selectable from "01" to "10"
Object Group
Group number of the DNP object in the target
- configurable within 0 to 255
Object Variation
Variation number of the DNP object in the target
- configurable within 0 to 255
Object Index
Index number of the DNP object in the target
- configurable within 0 to 65535
Channel Top
Top channel of MW100 which exchange data with DNP objects
- selectable within 001 to 060, A001 to A300 or C001 to C300
Channel Count
Channel count of MW100 which exchange data with DNP objects
- configurable within :
1 to 60 when 001 to 060 is set to top channel,
1 to 300 when 'A' or 'C' channel is set to top channel