2.5.1. Serial communication setting (YS)
This command is used to configure serial communication function. For implementing
DNP communication functions, new switches named DNP3_M and DNP3_S are added
to p1 parameter for enabling DNP master/slave functions.
- Setting to use device as Modbus
or DNP3
master / slave
13
YS p1, p2, p3, p4, p5
p1 : Function (MODBUS_M, MODBUS_S
, DNP3_M, DNP3_S
)
MODBUS_M
:
Modbus
master
MODBUS_S
:
Modbus
slave
DNP3_M
:
DNP
master
DNP3_S
: DNP
slave
p2 : Address (Modbus : 1 to 247
, DNP : 0 to 65519
)
p3 : Baud rate [bps] (1200, 2400, 4800, 9600, 19200, 38400,
57600, 115200)
p4 : Parity bits (NONE, EVEN, ODD)
NONE
:
No
parity
EVEN
:
Even
parity
ODD
:
Odd
parity
p5 : Stop bits (1, 2)
1
:
1
[bit]
2
:
2
[bit]
- Query
YS ?
13
Unless DNP option is specified, DNP3_M, DNP3_S can't be selected.