Yokogawa Standalone MW100 User Manual
Page 59

-
59/131 -
IM MW100-S16E-1
Ed01
Table 27. Parameters for configuring serial communication
Kind
Configuration
Function
Choice of serial function (driver)
- selectable from ”DNP 3.0 Master”, “DNP 3.0 Slave”
9
Address
DNP address of DNP master/slave function
- configurable within 0 to 65519
Baud Rate
Baud rate of serial communication [bps]
- selectable from ”1200”, “4800”, “9600”, “19200”, “38400”,
“57600”, “115200”
Parity Bit
Parity bits setting
- selectable from ”None”, “Odd”, “Even”
Stop Bit
Stop bits setting
- selectable from "1", "2"
Data Length
Bit size of character data
- fixed to 8 bits
Handshake Handshake
- fixed to off:off
9
If user choose other functions except for "DNP 3.0 Master" or "DNP 3.0 Slave", DNP
master or slave function will be stopped.