1 INTRODUCTION

1.1 Description

of

Unit

Thank you for purchasing the ¼ DIN Alpha COND 1000 series Conductivity
process controllers. This unit is used for measuring the Conductivity of a
solution, either in micro-Siemens or milli-Siemens, one at a time, and the
operational mode is switchable from the menu. You can use this unit to measure
Conductivity with limit control. This controller has many user-friendly and safety
features which include:

Menu-driven program that simplifies set-up

Ten ranges of Conductivity measurements-software selectable (Appendix
2
).

Built-in memory backup to ensure that calibration data and other
information are not erased if power supply fails

Automatic temperature compensation (ATC) with Pt100 or Pt 1000

Manual temperature compensation with independent setting for
calibration and process temperature

Temperature coefficient variable between 0.00 to 10.00 % per

o

C. Separate

pure water compensation curve stored in memory. Reference temperature
at 25

o

C.

• 0 to 1999 second time delay adjustment on all relays – minimise false

alarms

• Separately

adjustable

high and low set point hysteresis (dead bands)

prevents chattering of relays around the set points. Selectable Filter
function stabilises rapid measurement changes

Four operating modes: limit, display monitor , proportional pulse length or
proportional pulse frequency control.

Large dual display LCD for easy reading with clear multiple annunciators,
alarm status and operational message annunciators

Two switching contacts as set-point triggering relays and an alarm
output relay

• Separate

alarm relay alerts you when set points have exceeded the limits

and if the Pt100/Pt1000 wires are broken or disconnected during the ATC
function

Hold function freezes output current (0/4...20mA) and releases control
relays

LED indicators signal control activities to monitor controller status from a
distance

Protection against electromagnetic interference - galvanically isolated
0/4 - 20mA output provides safety for data logging and control purposes


1.2

Applications

Use this controller in panel mounted enclosures for applications in water treatment
and demineralization, waste water treatment and neutralization processes.