2 analog output forcing 31, 13 maintenance manager / error list 31, Forcing 31 – West Control Solutions SG 45 User Manual
Page 31: Maintenance manager 31

g
With measurement value or signal change with latch selected (
ConF / Lim / Fnc.x = 2, 4),
the alarm relay remains set, until it was reset in the error list,
This alarm can be reset via:
di1 or
a limit value
a key combination
or via interface (
Lim1 ... Lim3 = 1).
For this, reset value 0 must be specified in the error list or via the interface. ( r page 36).
g
After power on or an engineering download an used input filter has an effect on the gradient of the input
signal. Therefore a valid alarm monitoring can only be processed after a certain rise up time. This time
depends on the value of the filter time constant t.F.
For t.F = 0 the monitoring results are valid immediately.
Functions
31
Limit value processing
SG 45
LED
rot / red
t [min]
x
<L.1
{
{
x
t
Lim.1
H.1 = OFF