GALVANIC ISOLATION

Galvanic isolation between inputs and outputs as well as from
the supply voltage is provided.

Test voltages:

Between power supply and inputs/outputs:

2.3 kV AC, 1 min

Between inputs and outputs:

500 V AC; 1min

Max. permissible voltages:

Between inputs/outputs
against earth:

ß 33 V AC

POWER SUPPLY

Depending on ordered version:

AC supply

Voltage:

90...260 V AC

Frequency:

48...62 Hz

Consumption:

approx. 11.5 VA max.

Universal supply 24 V UC

AC supply:

18...30 V AC

Frequency:

48...62 Hz

DC supply:

18...31 V DC

Consumption:

approx. 8.5 VA / 5.8 W max.

* Instruments with optional system interface:
energization is via the bus connector from field bus coupler or
power supply module
cULus: class 2 only!

Behaviour with power failure

Configuration and parameter settings:Permanent storage in EEPROM

BLUEPORT

®

FRONT INTERFACE

Connection to the controller front via a PC adapter (see ‘Additional
Accessories’). The BlueControl

®

software enables the KS 45 to be

configured, parameters set, and operated.

BUS INTERFACE (OPTIONAL)

RS 485

Connection via bus connector fitted in the top-hat rail. Screened
cables should be used.

Type:

RS 485, copper

Transmission speed:

2,400, 4,800, 9,600, 19,200,
38,400 Bit/sec

Parity:

even, odd, none

Address range:

1...247

Number of controllers per bus
segment:

32

Moreover, repeaters must be used.

Protocol

MODBUS RTU

SYSTEM INTERFACE

For connection to fieldbus couplers
(see system components)
Connection via bus connector fitted in the top-hat rail.
Technical data see data sheet 9498-737-50911.

Technical data

53

UNIFLEX SG 45

safety isolation
functional isolation

Power

relay OUT1

Input INP

di 1 (contact)

Output OUT3

RS 485

System

relay OUT2

Front interface