12 technical data, Inputs signal input inp, Digitalinput di1 – West Control Solutions SG 45 User Manual

Page 52: Outputs relay outputs out1, out2, Out3 as universal output

Advertising
background image

.

12

Technical data

INPUTS

SIGNAL INPUT INP

Accuracy:

0,01% at 25°C

Decimal point:

0 bis 3 decimals

Input filter:

adjustable 0.0...999.9 s

Scanning cycle:

50 ms with 19 bit

Linearization:

31 Segments, adaptable with
BlueControl

®

Calibration:

with/without shunt calibration

Measurement value cor-
rection:

2-point

Limiting frequency

1.7Hz

Measurement value cor-
rection:

Sensor break, short circuit and po-
larity

Connection technology:

4-wire bridge
6-wire bridge (Sense line)

Input range
Span start, span end

any, within measuring range

Scaling

any, -1999 ...9999

Measurement span:

with Us = 10V

Slope/ sensitivity

0.5 mV/V

5 mV

1 mV/V

10 mV

2 mV/V

20 mV

4 mV/V

40 mV

DIGITALINPUT DI1

Operation as

Contact input

Connection of a potential-free contact that is suitable for
switching ‘dry’ circuits.

Switched voltage:

5 V

Current:

0.5 mA

Function

Configurable as direct or inverse switch or push button!

Functions:

Operation disabling, reset of stored alarms and the
min/max indicator (slave pointer), the integrator,
enabling the tare function,Sample&Hold amplifier
function, Cal-Test , and zero setting.

OUTPUTS

RELAY OUTPUTS OUT1, OUT2

Contact type:

2 normally open with common
contact connection

Max. contact rating:

500 VA, max. 250 V, max. 2A
at 48...62 Hz, ohmic load

Min. contact rating:

6V, 1 mA DC

Swithing cycles (electrical):

for I=1A/2A: ?
800,000/500,000 (at~250V
(ohmic load))

Note:

If the relays OUT1, 2 and 3 are used to operate external contac-
tors, these must be fitted with RC snubber circuits to manufactu-
rer specifications to prevent excessive voltage peaks at
switch-off.

OUT3 AS UNIVERSAL OUTPUT

Parallel current/voltage output with common ‘minus’ terminal
(combined use only in galvanically isolated circuits).

Freely scalable
Resolution:

14 Bit

Dynamic response

(step change of input signal) T

90

:

Output follows the in-
put within 300 ms

Tracking error I/U:
Residual ripple:

(rel. to range end)

£ 2 %

ß_1%
0...130 kHz

Current output

0/4...20 mA, configurable, short-circuit proof.

Control range:

-0.5....23 mA

Load:

£ 600 [

Load effect:

ß0.02%

Resolution:

ß 1.5 úA

Error:

ß 0.1%

Voltage output

0/2...10V, configurable, not permanently short-circuit proof
Control range:

0.15...11.5 V

Load:

? 2 k[

Load effect:

ß0.06%

Resolution:

ß 0.75 mV

Error:
Additional error when using simultaneous-
ly the current output

Я 0.1%

Я+0.09%

Output values can be preset via interface (Forcing)

Technical data

UNIFLEX SG 45

52