26

5. Select Cal[OFF] E=ON, press or select E once to

change OFF to ON. (NOTE: Make sure the Flow Detector
Pipe is Empty.)

NOTE: With the pipe empty the usage reading should
be between 3.00 and 3.30 Volts.

6. Select Exit WITH save. Press E once to save the setting

and return to EMPTY PIPE 15.

7. In EMPTY PIPE 15, select Cal. full pipe. Then, press E.

9. Select Cal[OFF] E=ON, press or select E once to change

to OFF to ON.

(NOTE: Make sure the Flow Detector pipe

is full of fl uid.)

NOTE: The full pipe voltage reading should be below
3.00 Volts.

10. Press + once to move cursor to Exit WITH save. Press E

once to save the setting and return to EMPTY PIPE 15.

11. In EMPTY PIPE 15, press + three times to place cursor

at Enable/Disable. Next, press E.

12. In EMPTY CONTROL 1G, press + twice to move cursor

to Det[OFF] E=ON. Press E once to switch OFF to ON.

13. Press + once to move cursor to Exit WITH save. Press E

once to save the setting and return to EMPTY PIPE 15.

Pulse Output

1. Press E once to move cursor to Main Menu.

2. In the MAIN MENU 00, press + three times to move the

crusor to Inputs/Outputs. Next, press E.

3. At IN/OUTPUTS 30 press + three times to place the

cursor at Digital Out. #1. Press E.

4. In DIG OUTPUT 1 33, press + once to move the cursor

to Pulses / unit. Press E.

You only need to do this if the function of output one (1) is
to be Fwd Pulse or AMR (50ms pulse.) (Refer to page 36 -
"Digital Out #1.")

5. In PULSES/UNIT 3D input a proper number as

described earlier. Press E.