28

5.When Select Function is selected, screen Z1 appears for

two seconds.

6. It then switches to SELECT OUT #1 3J. Make a selection.

Press E.

7. This type of screen shows for two seconds and then

returns to DIG OUTPUT 1 33.

Whichever selection is made from screen SELECT OUT #1 3J,
the next screen always shows XXXXX ** SELECTED**.

The screen then returns to DIG OUTPUT 1 33 where you will

have to:

1. Select Functions screen

2. Screen Z1 appears

3. Select another screen

Do this until all required Digital Outputs are programmed.

There are four Digital Outputs in this program. Perform the
same for all of them, if applicable. (Note that not all output
functions are available on all outputs.)

Analog Output

1. Press E once to move cursor to Main Menu.

2. In the MAIN MENU 00, press + three times to move the

cursor to Inputs/Outputs. Next, press E.

3. At IN/OUTPUTS 30 press + once to place the cursor at

Analog Output. Press E.

4. In ANALOG OUTPUT 31 press + once to move the

cursor to Range Select. Press E.

5. In RANGE SELECT 3A select a range with the + button

and then press E.

6. The screen returns to ANALOG OUTPUT 31. Press + twice

to move the cursor to Zero Calibrate and then press E.

Connect amp meter to mA analog output pins 9 and 10.

7. In ANALOG ZERO 3B make a selection of Decrease or

Increase based on what the amp meter is reading.

8. Press

the

E button until the amp meter reads the desired

No Flow set point. (The line to the left of the selection
rotates as the E button is pressed, to show that there is
activity.)