6. The screen returns to DIG OUTPUT 1 33. Press or

activate + twice, then press E.

This is only for Fwd Pulse. (Refer to page 36 - "Digital Out
#1.")

7. Into screen PULSE WIDTH 3E enter a number. Press E.

8. The screen returns to DIG OUTPUT 1 33. Press + three

times, then press E.

SET POINT

This is only for Flow Set Point. (Refer to page 36 - "Digital
Out #1.")

1. Into screen SET PT. MIN 3F enter a number.

NOTE: When the fl ow rate falls below the minimum set point

value (entered as a percentage of full scale,) the output
activates.

2. The Screen returns to DIG OUTPUT 1 33. Press + four

times, then press E.

3. In SET PT. MAX 3G enter a number.

NOTE: When the fl ow rate exceeds the set point max.
value (entered as a percentage of full scale fl ow) the output
activates.

This is only for Flow Set Point. (

Refer to page 36 - "Digital

Out #1.")

OUTPUT TYPE
1. Press or activate the letter E to return to screen DIG

OUTPUT 1 33.

2. In DIG OUTPUT 1 33 press + fi ve times, to Output Type.

3. In OUTPUT TYPE 3H press Normally Open or Normally

Closed.

Select N.O. or N.C. for any output. (Refer to page
36, "Digital Output #1.")

• Normally Opened or Closed **Selected** shows

for two seconds.

• The screen goes back to DIG OUTPUT 1 33.

4. Pres + six times, or - once to Select Function.